Technical data and accessories

Model DH 15 AX DH 30 AX DH 60 AX DH 60 AHP DH 75 AX DH 110 AX
Dehumdification performance
see table see table see table see table see table see table
Voltage V / Current A 230 / 3.8 230 / 3.4 230 / 5.6 230 / 5.3* 230 / 6.4 230 / 9.3
Starting current A (fuse) 18 (10) 20 (16) 30 (16) 30* (16*) 55 (13) 66 (20)
Power input** (kW) 0.43 0.75 1.2 1.1* 1.46 2.1
Heat emission** (kW) 1.2 2 3.5 2.2* 4.0 5.2
Efficiency (C.O.P.) 3.0 2.3 2.8 2.8 2.3 2.3
Refrigerant R-407C R-134a R-407C
Air flow rate free blow out (m³/h)
225 390 750 1,750 1,180 1,180
Sound level (distance 1 m) dBA
53 46 47 57 53 53
Operating range temperature
0 to 40 °C 0 to 40 °C 0 to 40 °C 15 to 55 °C 5 to 40 °C 5 to 40 °C
Operating range max. r.h.
90 °C 90 °C 90 °C 90 °C 90 °C 90 °C
Lenght (mm) 360 290 290 240 1,437 1,437
Width (mm) 817 875 1,300 1,245 325 325
Height (mm) 320 745 745 653 729 729
Weight (kg) 35 55 70 70 132 134
Automatic melting mechanism
yes yes yes ** yes yes
Integrated hygrostat yes yes yes external*** yes yes
Temperature limit indicator - - - external*** - -
Heat recovery - optional optional - - -
Heat emission to water max. kW
- 1.5 2.8 - - -
Condensation drain connection
9.5 mm 15 mm 15 mm 15 mm 15 mm 15 mm
* Values refer to operation without switching on of the integrated 4 kW (DH 60 AHP) or 9 kW (DH 300 BH) electrical heating units respectively. ** at 20 °C and 75 % r.h. *** offcycle defrost **** Control of climate conditions and also any ventilation units that may be present takes place via an external control cabinet.

Model DH 110 BX DH 150 AX DH 150 BX DH 300 BH DH 300 BY DH 600 BY
Dehumdification performance
see table see table see table see table see table see table
Voltage V / Current A 400 / 4.2 230 / 19 400 / 8.3 400 / 9* 400 / 16 400 / 30
Starting current A (fuse) 30 (10) 61 (25) 30 (16) 72* (25*) 69 (25) 135 (45)
Power input** (kW) 2.1 2.5 2.5 5.1* 6.7 10
Heat emission** (kW) 5.2 6.5 6.5 10* 16 28
Efficiency (C.O.P.) 2.3 2.6 2.6 2.7 2.7 2.7
Refrigerant R-407C R-134a R-407C
Air flow rate free blow out (m³/h)
1,180 2,300 2,300 5,800 5,000 9,000
Sound level (distance 1 m) dBA
53 58 58 69 66 63
Operating range temperature
5 to 40 °C 0 to 40 °C 0 to 40 °C 15 to 70 °C -15 to 40 °C -15 to 40 °C
Operating range max. r.h. 90 °C 90 °C 90 °C 90 °C 90 °C 90 °C
Lenght (mm) 1,437 660 660 700 720 1,250
Width (mm) 325 660 660 985 980 1,730
Height (mm) 729 1,313 1,313 1,476 1,435 1,600
Weight (kg) 134 130 130 170 220 497
Automatic melting mechanism
yes yes yes ** yes yes
Integrated hygrostat - yes yes external*** yes yes
Temperature limit indicator - yes yes external*** yes yes
Heat recovery - optional optional - optional optional
Heat emission to water max. kW
- 7 7 - 15 30
Condensation drain connection
- 24 mm 24 mm 45 mm 45 mm 45 mm
* Values refer to operation without switching on of the integrated 4 kW (DH 60 AHP) or 9 kW (DH 300 BH) electrical heating units respectively. ** at 20 °C and 75% r.h. *** offcycle defrost **** Control of climate conditions and also any ventilation units that may be present takes place via an external control cabinet.

Available accessories (model-dependent):
High-pressure fans, air filters, external condenser unit, air distributor (also with built-in electric heater 9-18 kW), stainless steel version, Remote control, various control units and control cabinets. Further accessories and special configurations on request.